Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety)
  • Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety),MY SHOP,Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety)
  • Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety),MY SHOP,Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety)
  • Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety),MY SHOP,Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety)
  • Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety),MY SHOP,Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety)
  • Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety),MY SHOP,Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety)
  • Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety),MY SHOP,Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety)

Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety)

Download
View all downloads
  • Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety),MY SHOP,Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety)
  • Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety),MY SHOP,Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety)
  • Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety),MY SHOP,Schneider Electric France Vigilohm Series IT System Insulation Monitor (Industrial Power Distribution Safety)

Description

Schneider Electric (France) Vigilohm Series IT‑System Insulation Monitoring Device (Industrial Distribution Safety)

Complete Specification

I. Brand and Product Positioning

Schneider Electric Vigilohm delivers a complete Insulation Monitoring Device (IMD) solution dedicated to IT ungrounded systems, belonging to the PowerLogic power‑distribution safety portfolio. Core technology originates from France, and the full product range is available in China. Compliant with IEC 61557‑8 and mandatory Chinese GB standards for medical and industrial electrical safety. Adopting low‑frequency AC injection measurement method, it is compatible with complex power grids featuring high stray capacitance, including AC, DC, mixed AC‑DC systems, frequency converters, photovoltaic and energy‑storage installations. It performs 24‑hour online monitoring of phase‑to‑earth insulation resistance. A single earth‑fault will not trigger tripping to guarantee continuous production. When paired with fault‑location modules, faulty branches can be rapidly identified. Modbus communication enables integration into the EcoStruxure power‑monitoring platform, covering industrial, medical, new‑energy, marine and rail‑transit applications.

II. Core Measuring Principle

A low‑amplitude low‑frequency measuring signal is injected between the IT system and protective earth (PE). Leakage current in the loop is sampled to calculate insulation resistance. Built‑in adaptive digital filtering for stray capacitance compensates interference caused by long cables and frequency converters for drift‑free measurement. Periodic automatic full‑unit self‑test and monitoring‑wire breakage detection eliminate blind spots of monitoring‑circuit failure. The measuring voltage is low and imposes no disturbance to the host system.

III. Main Product Portfolio

  • Vigilohm IM10 / IM20 Economy General‑purpose Models (Small control cabinets, machine tools, UPS) ‑ IM10: Basic variant, displays insulation resistance only. Single‑stage adjustable alarm threshold. Narrow DIN‑rail housing for low‑voltage small‑scale AC/DC IT loops. ‑ IM20: Upgraded variant, shows both insulation resistance and system‑to‑earth stray capacitance. Dual‑alarm outputs (pre‑alarm + fault alarm) with passive relay contacts. Suitable for installations with frequency converters and long cables.

Applications: machine‑tool control loops, elevators, small isolated UPS, 24 V industrial‑control isolated power supplies.

  • Vigilohm IM10‑H / IM20‑H Medical‑specific Models (Operating rooms, ICUs) Compliant with mandatory medical standard IEC 60364‑7‑710, designed for use with medical isolation transformers. Simultaneously monitors insulation resistance, transformer winding overload and winding temperature (PTC / PT100 temperature sensing supported). Dual‑level audible‑visual alarms. External remote nurse‑station alarm panel is supported to ensure uninterrupted power supply for surgical environments.
  • Vigilohm IM400 High‑end Digital Flagship (Main unit for PV, energy‑storage, chemical and marine applications) Full‑range digital multi‑function platform with multiple derivative variants: ‑ IM400 Standard: Universal AC/DC capability, max DC 1200 V. LCD display for insulation resistance, earth‑stray‑capacitance values and fault history. ‑ IM400C: Conformal‑coated rugged version for humid, dusty and corrosive cabinet environments. ‑ IM400L: 24/48 VDC auxiliary power supply, dedicated for on‑board equipment and energy‑storage containers. ‑ IM400THR Medium‑voltage expansion unit: Works with voltage adapters for medium‑voltage IT‑system monitoring.

Key features: Modbus RTU communication, time‑stamped fault logs, insulation‑resistance trend curves, 4‑20 mA analog output for PLC transmission. High stray‑capacitance tolerance, suitable for multi‑inverter energy‑storage plants and 1500 V PV DC busbars.

  • IFL12MCN Multi‑branch Insulation‑fault Locator (for use with IM400) Accurately pinpoints faulty branches in multi‑loop IT systems without segment‑by‑segment power‑off troubleshooting. Standard equipment for large‑scale factories, energy‑storage power stations and multi‑workshop distribution systems.
  • High‑voltage Voltage Adapters Raise the maximum measurable voltage of the master unit, supporting AC 1700 V and DC 1200 V high‑voltage DC systems for energy‑storage stations, charging piles and wind‑turbine high‑voltage busbars.

IV. Core Functions & Technical Advantages

‑ Wide‑range Anti‑interference Performance: Adaptive compensation for system‑to‑earth stray‑capacitance, preventing false alarms in complex environments with multiple frequency converters, long DC cables, photovoltaic and energy‑storage equipment. Universal for mixed AC‑DC systems; no separate AC‑ or DC‑specific model selection required. ‑ Dual‑level Alarm Mechanism: Level‑1 pre‑alarm warns of gradual insulation degradation for planned maintenance. Level‑2 fault alarm triggers safety interlock upon insulation breakdown. Relay normally‑open / normally‑closed contacts are user‑configurable. ‑ Comprehensive Safety Self‑check: Automatic periodic full‑unit self‑test, monitoring‑wire breakage detection and hardware‑fault alarm. Fault records are stored permanently and retained after power loss. ‑ Complete Digital Output Options: Passive relay dry contacts, 4‑20 mA analog output and Modbus RTU. Seamless data integration with Schneider EcoStruxure, third‑party SCADA and cloud‑operation platforms. ‑ Modular Cabinet‑ready Design: DIN‑rail mounting across the full series, plug‑in terminal blocks for neat cabinet wiring. Expansion and replacement do not require distribution‑panel modification. ‑ Full‑range Industry Certifications: CE, UL, DNV marine approval and medical‑specific certifications, complying with domestic mandatory monitoring requirements for IT power distribution, photovoltaic and medical facilities.

V. Typical Application Industries

‑ Medical: IT isolated power‑supply systems for operating rooms, ICUs and anaesthesia rooms (IM10‑H / IM20‑H). ‑ New‑energy: Insulation monitoring for PV DC combiner boxes, DC 1200 V energy‑storage busbars and high‑voltage DC charging piles (IM400). ‑ Industrial Automation: Machine tools, frequency converters, explosion‑proof chemical isolated power supplies and UPS uninterruptible systems. ‑ Marine & Rail Transit: Marine DC power grids and train traction isolation systems. ‑ Infrastructure: Continuous‑power‑supply safety monitoring for tunnels, ports, airports and oil‑gas explosion‑hazard zones.

VI. List of Matching Accessories

‑ IFL12MCN multi‑branch insulation‑fault locator ‑ High‑voltage expansion voltage adapters ‑ Medical remote audible‑visual alarm panel ‑ Modbus communication gateway and host‑computer data‑recording software ‑ Conformal‑coating kits, DIN‑rail mounting hardware, test‑and‑reset push‑buttons

VII. Supply Information

Economical IM10 / IM20 models are available from local stock. Digital flagship IM400, complete medical‑grade IM10‑H sets, fault‑location modules and high‑voltage adapters are sourced from original manufacturer. Accurate type‑selection and quotation can be provided according to system voltage, AC/DC type, medical / explosion‑proof requirements and communication specifications.