Founded in Freiburg, Germany in 1928, DOLD is a world‑class manufacturer of high‑end safety‑monitoring relays. The VARIMETER IMD insulation‑monitoring series delivers standardized solutions for IT ungrounded systems, with a production base located in Taicang, China. Compliant with IEC 61557‑8, VDE and Chinese national standards. Adopting adaptive pulse measurement technology, it can tolerate system‑to‑earth stray capacitance up to 3000 μF. Suitable for complex mixed AC‑DC IT power grids such as frequency converters, photovoltaic DC systems, DC charging piles, medical facilities and marine vessels. It monitors phase‑to‑earth insulation resistance in real‑time. A single earth‑fault will not interrupt production, and early warnings are generated for cable aging and insulation breakdown. Integrated functions including fault location, Modbus communication and analog signal transmission are available.
The device superimposes low‑frequency test measurement voltage onto the IT system and calculates insulation resistance by collecting earth‑leakage current. Built‑in adaptive compensation algorithm for stray capacitance automatically offsets interference caused by frequency converters and long cables, ensuring drift‑free measurement with response time ≤ 1 s. It performs 24‑hour continuous online monitoring, and simultaneously detects breakage of measurement wiring and internal instrument failures for dual‑safety self‑check.
‑ High Stray‑capacitance Compatibility: Tolerates system‑to‑earth capacitance up to 3000 μF, no false alarms with long cables and multiple frequency converters, offering excellent system adaptability. ‑ Two‑stage Graded Alarms: Pre‑alarm indicates insulation degradation for scheduled maintenance in advance; fault alarm triggers safety interlock. Relay supports de‑energized / energized alarm modes. ‑ Comprehensive Fault Self‑check: Automatic daily full‑unit self‑test, measurement‑wire breakage detection and internal hardware‑fault alarm, eliminating blind spots of monitoring‑circuit failure. ‑ Diverse Digital Outputs: Analog transmission, passive relay dry contacts and Modbus RTU. Insulation values and fault codes can be uploaded to SCADA and cloud platforms. ‑ Modular Standard DIN‑rail Installation: Multiple housing widths from 18 mm to 90 mm for option, delivering neat cabinet wiring and convenient later‑stage expansion. ‑ Full‑range Industry Certifications: CE, UL, CSA plus special certifications for medical, marine and new‑energy applications, meeting mandatory electrical‑safety specifications for IT systems.
‑ New‑energy Sector: Insulation monitoring for PV DC combiner boxes, energy‑storage DC 1000 V busbars and DC charging piles. ‑ Medical Sector: Supporting monitoring for IT isolated power supplies in operating rooms and ICUs. ‑ Industrial Automation: Ungrounded control loops for machine tools, elevators, frequency converters and UPS. ‑ Marine & Rail Transit: Marine DC power grids and train traction isolation systems. ‑ Chemical & Explosion‑proof Industries: Explosion‑proof isolated power supply and reactor frequency‑converter drive loops. ‑ Mobile Equipment: Isolated power supplies for mobile generator sets, port gantry cranes and construction machinery.
‑ RL/RP5898 high‑voltage expansion couplers ‑ Multi‑branch insulation‑fault locator units ‑ External test‑reset push‑buttons and audible‑visual alarm panels ‑ Modbus communication gateways and parameter‑configuration software ‑ Various DIN‑rail mounting hardware and terminal‑block kits
Economical IL5880 is available from local stock; universal LK5895 has sufficient inventory. Digital communication‑type RN5897, high‑voltage couplers and fault‑location modules are ordered from the original German manufacturer. Accurate type‑selection and quotation can be provided according to system voltage, AC/DC type and communication requirements.