Germany DOLD VARIMETER IMD Insulation Monitor
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor

Germany DOLD VARIMETER IMD Insulation Monitor

Download
View all downloads
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor
  • Germany DOLD VARIMETER IMD Insulation Monitor,MY SHOP,Germany DOLD VARIMETER IMD Insulation Monitor

Description

DOLD, Germany VARIMETER IMD Insulation Monitoring Device Complete Specification

I. Brand Overview

Founded in Freiburg, Germany in 1928, DOLD is a world‑class manufacturer of high‑end safety‑monitoring relays. The VARIMETER IMD insulation‑monitoring series delivers standardized solutions for IT ungrounded systems, with a production base located in Taicang, China. Compliant with IEC 61557‑8, VDE and Chinese national standards. Adopting adaptive pulse measurement technology, it can tolerate system‑to‑earth stray capacitance up to 3000 μF. Suitable for complex mixed AC‑DC IT power grids such as frequency converters, photovoltaic DC systems, DC charging piles, medical facilities and marine vessels. It monitors phase‑to‑earth insulation resistance in real‑time. A single earth‑fault will not interrupt production, and early warnings are generated for cable aging and insulation breakdown. Integrated functions including fault location, Modbus communication and analog signal transmission are available.

II. Measuring Principle

The device superimposes low‑frequency test measurement voltage onto the IT system and calculates insulation resistance by collecting earth‑leakage current. Built‑in adaptive compensation algorithm for stray capacitance automatically offsets interference caused by frequency converters and long cables, ensuring drift‑free measurement with response time ≤ 1 s. It performs 24‑hour continuous online monitoring, and simultaneously detects breakage of measurement wiring and internal instrument failures for dual‑safety self‑check.

III. Main Product Portfolio

  • IL5880 / IP5880 Economy Basic Models (For small control cabinets) Narrow‑body DIN‑rail mounting, applicable for single‑phase / three‑phase IT systems AC 0~500 V. Single‑stage alarm adjustable via potentiometer, LED status indicators. Continuous monitoring is available even when the system is de‑energized. Applied for machine tools, small UPS and 24 V industrial‑control isolated loops.
  • LK5895 / LK5896 Universal Mainstream Models Covers AC, DC and mixed AC‑DC systems up to DC 1000 V. Two independently adjustable thresholds (pre‑alarm: 20 kΩ2 MΩ; fault alarm: 1 kΩ250 kΩ). Three relay outputs (pre‑alarm, fault, instrument wire‑break self‑check). Supports 010 V / 420 mA analog transmission for PLC upload. LED bar‑graph directly displays real‑time insulation resistance values. Suitable for photovoltaics, energy‑storage systems, frequency‑converter drives and chemical DC equipment. External couplers can be used for high‑voltage system expansion.
  • RN5893 / RN5897 High‑end Digital Flagship Models Equipped with LCD digital display for accurate insulation‑resistance readout. Standard Modbus RTU communication for remote parameter read‑write and fault‑record storage. Sealed transparent protective cover prevents unauthorized parameter modification. Provides trigger output for fault‑location and can work with branch fault‑locator units. Wide operating temperature: ‑40 ℃ ~ +70 ℃. Specially designed for new‑energy DC charging piles and large‑scale energy‑storage cabinets, complying with mandatory charging‑pile standard IEC 61851.
  • High‑voltage Expansion Couplers RL5898 / RP5898 ‑ RL5898: Expansion for AC400V / DC500V ‑ RP5898: Expansion for AC690V / DC1000V No host replacement required. Realizes insulation monitoring for high‑voltage IT systems via couplers. Dedicated for wind‑power and marine high‑voltage DC applications.
  • Matching Branch Insulation‑fault Locator Module Used in multi‑loop IT systems to accurately identify which load branch suffers insulation damage. No segment‑by‑segment power‑off troubleshooting required, greatly shortening maintenance time.

IV. Core Functional Advantages

‑ High Stray‑capacitance Compatibility: Tolerates system‑to‑earth capacitance up to 3000 μF, no false alarms with long cables and multiple frequency converters, offering excellent system adaptability. ‑ Two‑stage Graded Alarms: Pre‑alarm indicates insulation degradation for scheduled maintenance in advance; fault alarm triggers safety interlock. Relay supports de‑energized / energized alarm modes. ‑ Comprehensive Fault Self‑check: Automatic daily full‑unit self‑test, measurement‑wire breakage detection and internal hardware‑fault alarm, eliminating blind spots of monitoring‑circuit failure. ‑ Diverse Digital Outputs: Analog transmission, passive relay dry contacts and Modbus RTU. Insulation values and fault codes can be uploaded to SCADA and cloud platforms. ‑ Modular Standard DIN‑rail Installation: Multiple housing widths from 18 mm to 90 mm for option, delivering neat cabinet wiring and convenient later‑stage expansion. ‑ Full‑range Industry Certifications: CE, UL, CSA plus special certifications for medical, marine and new‑energy applications, meeting mandatory electrical‑safety specifications for IT systems.

V. Typical Application Industries

‑ New‑energy Sector: Insulation monitoring for PV DC combiner boxes, energy‑storage DC 1000 V busbars and DC charging piles. ‑ Medical Sector: Supporting monitoring for IT isolated power supplies in operating rooms and ICUs. ‑ Industrial Automation: Ungrounded control loops for machine tools, elevators, frequency converters and UPS. ‑ Marine & Rail Transit: Marine DC power grids and train traction isolation systems. ‑ Chemical & Explosion‑proof Industries: Explosion‑proof isolated power supply and reactor frequency‑converter drive loops. ‑ Mobile Equipment: Isolated power supplies for mobile generator sets, port gantry cranes and construction machinery.

VI. Matching Accessories

‑ RL/RP5898 high‑voltage expansion couplers ‑ Multi‑branch insulation‑fault locator units ‑ External test‑reset push‑buttons and audible‑visual alarm panels ‑ Modbus communication gateways and parameter‑configuration software ‑ Various DIN‑rail mounting hardware and terminal‑block kits

VII. Supply Information

Economical IL5880 is available from local stock; universal LK5895 has sufficient inventory. Digital communication‑type RN5897, high‑voltage couplers and fault‑location modules are ordered from the original German manufacturer. Accurate type‑selection and quotation can be provided according to system voltage, AC/DC type and communication requirements.